Analog Programming (APG) and Isolated Analog Programming (ISOL) 
 
4-12  M370430-01  Rev B 
Voltage-Controlled Current APG Setup 
Activating APG Current Mode 
To activate APG current mode using an external voltage source: 
1.  Turn the 9-position mode control to the CAP position or press 
the rotary Adjust/Enter control if the mode control is already 
at the CAP position. 
 is displayed on the output voltage display. 
2.  Turn the rotary Adjust/Enter control to select source   
(Voltage source from non-isolated connector). 
3.  Press the rotary Adjust/Enter control to commit the selected 
mode.   is displayed on the output voltage display. 
4.  Select the input source level using the rotary Adjust/Enter 
control. 
5.  Once the desired level has been selected, press the rotary 
Adjust/ Enter control to commit the change. 
The display will return to the normal display. 
Deactivating APG Current Mode 
To deactivate the APG current mode: 
1.  Turn the 9-position mode control to the CAP position or press 
the rotary Adjust/Enter control if the mode control is already 
at the CAP position. 
2.   is displayed on the output voltage display. 
3.  Turn the rotary Adjust/Enter control to select  . 
4.  Press the rotary Adjust/Enter control to commit the change.  
The display will return to the normal display.