Installation 
 
M370430-01  Rev B  2-15 
Step 7: Connecting Remote Sensing 
WARNING: Shock hazard 
There is a potential shock hazard at the sense connectors when using a power 
supply at an output greater than 40 V. Select wiring with a minimum insulation 
rating equivalent to the maximum output voltage of the power supply for use as 
local sense jumpers or for remote sense wires. Ensure that connections at the 
load end are shielded to prevent contact with hazardous voltages. 
 
Remote sensing permits you to shift the regulation point of the 
power supply from the output terminals to the load or other 
distribution terminals. 
Use shielded twisted pair wiring of 20 to 26 AWG for best noise 
performance. Make sure that the shielded twisted pair wiring insulation 
is rated higher than the maximum output voltage of the power supply. If 
possible, one end of the shield of the sense lines should be attached to 
the chassis ground of the power supply. 
 
 
Figure 2-5  Remote Sense Connection 
To connect the remote sense wires: 
1.  Ensure that the front panel power switch is in the Off position. 
2.  Using a small flat blade screwdriver, remove the two sense 
jumpers from pins J1.1 and J1.2, and from pins J1.5 and J1.6 
on the APG Connector. See Figure 4-1, “APG Connector 
Terminals” on page 4-5. 
Pin J1.1 on APG 
connector 
Output terminals on 
power supply 
Pin J1.6 on APG 
connector