Local Operation 
 
M370430-01  Rev B  3-49 
Connecting to the Load in Remote Sensing Mode 
Connect the negative (-) output terminal of one power supply to the 
positive (+) output terminal of the next power supply. The more 
positive supply's positive sense line should connect to the positive 
terminal of the load (or distribution point). Its return sense line 
should connect to the connection between the two units at the same 
spot as the negative supply's positive sense line. The return sense 
line of the negative supply should be connected to the return of the 
load. See Figure 3-6. 
CAUTION: Equipment damage 
Do not connect sense lines through relays. 
 
 
Figure 3-6  Load Connections in Remote Sensing Mode