Local Operation 
 
3-28  M370430-01  Rev B 
Using Over Voltage Protection (OVP) 
The OVP circuit protects the load in the event of an analog 
programming error, an incorrect voltage control adjustment, or a 
power supply failure. The OVP circuit monitors the output voltage 
at the output of the power supply and will disable the output 
whenever a preset voltage set point is exceeded. You can set the 
preset voltage trip point by using the 9-position mode control on 
the front panel or via one of the remote programming interfaces. 
To prevent accidental tripping of the OVP while setting up, the 
firmware will prevent the OVP set point from being less than 
105% of the voltage set point when in local set point control mode. 
When the XG/XTR is in VAP mode for defining voltage set point 
the set point limitation will be based on the VAP input signal level. 
The user should note it is possible to trip OVP in this mode if the 
OVP is configured when the analog programming source is off. 
When the user attempts to configure an OVP setpoint that is less 
than 105% of the voltage set point via the front panel the set point 
will stop allowing the value to decrement. If the user attempts to 
configure an OVP set point that is less than 105% of the voltage set 
point via SCPI a -221, “settings conflict error” will be pushed onto 
the error queue.