Local Operation 
 
3-34  M370430-01  Rev B 
Defining the Polarity of the External Shutdown Signal 
1.  Turn the 9-position mode control to the PRT position or press 
the rotary Adjust/Enter control if the control knob is already 
at the PRT position. 
 is displayed on the output voltage display. 
2.  Turn the rotary Adjust/Enter control until   is 
displayed. 
3.  Press the rotary Adjust/Enter control to display   
(shutdown on logic 0) or   (shutdown on logic 1). 
4.  Press the rotary Adjust/Enter control to commit the desired 
polarity setting. 
For example: If you set the shutdown logic to 1 ( ) and apply a 
logic high (greater than 1.2 Vdc) to pin J3.12 relative to pin J3.6 on 
the ISOL connector, the power supply will shut down. Conversely, 
if you set the shutdown logic to 0 ( ), the power supply will 
only operate when you have a logic high (greater than 1.2 Vdc) to 
pin J3.2 relative to pin J3.6. 
Important:  There is an internal pullup resistor inside the shutdown circuit so 
the shutdown polarity should be set to 0 if it is not being used. 
The SCPI command (s) for these instructions are: 
[:]OUTPut[<channel>]:POLarity 
Loop Protection (version 2.21 and higher) 
The Loop Protection feature can be used to enable or disable multiple 
units in daisy chain configuration through the AUX Output and Isolated 
Analog Programming Connector, J3. Up to four units (example, Units 
#1 through #4) can be configured in Loop Protection; if one of the units 
is experiencing a fault condition, other units in the same loop will 
disable their output simultaneously. This is achieved by connecting Unit 
#1’s MAIN_PS_GOOD to Unit #2’s SD (Shutdown Main O/P) and 
continues until Unit #4’s MAIN_PS_GOOD is fed to Unit #1’s SD 
(Shutdown Main O/P). Common applications include single master 
controlling multiple slave units as a system On/Off. In addition, any 
fault from either operating unit will cause the system to disable. 
The Loop Protection can be enabled or disabled locally using the front 
panel 9-position mode control, or remotely using a SCPI command. 
Important:  While Loop Protection is enabled (ON), the external shutdown 
function will be automatically set to low active. When Loop Protection is 
disabled (OFF), the external shutdown function will be set to the user’s last 
setting.