Local Operation
3-20 M370430-01 Rev B
9. Press the rotary Adjust/Enter control to commit the Constant
Power operation.
To disable Constant Power operation:
1. Turn the 9-position mode control to the FLD position or press
the rotary Adjust/Enter control if the 9-position mode control
is already at the FLD position.
2. ” is displayed on the output voltage display and the
output current display shows the Constant Power mode.
3. Turn the rotary Adjust/Enter control until is displayed
in the output current display.
4. Press the rotary Adjust/Enter control to commit the setting
once the desiredvalue has been set.
5. The green FLD LED will turn off and the display will return
to the normal display mode.
The SCPI command (s) for these instructions are:
[:]SOURce[<channel>]:POWer:MODe[:STATe]
[:]SOURce[<channel>]:POWer:LEVel