EasyManua.ls Logo

Automationdirect.com Stride SIOL-EI8B - IO-Link Device Diagnostic

Automationdirect.com Stride SIOL-EI8B
117 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SIOL-EI8B-USER-M
62
Operation Powered by
Version 1, May 2022
9.2.3.7. IO-Link device diagnostic
IO-Link Device Diagnostic (Global Error Code 0x41)
Description Value
Error 0x0000
General Malfunction 0x1000
Temperature Fault 0x4000
Ambient Temperature: General Error 0x4100
Ambient Temperature: Over-Run 0x4110
Ambient Temperature: Under-Run 0x4120
Device Temperature: General Error 0x4200
Device Temperature: Over-Run 0x4210
Device Temperature: Under-Run 0x4220
Outside Temperature: General Error 0x4300
Outside Temperature: Over-Run 0x4310
Outside Temperature: Under-Run 0x4320
Device Hardware Fault 0x5000
Component Malfunction 0x5010
Non Volatile Memory Loss 0x5011
Batteries Low 0x5012
General Power Supply Fault 0x5100
Fuse Blown/Open 0x5101
Primary Supply Voltage Over-Run 0x5110
Primary Supply Voltage Under-Run 0x5111
Secondary Supply Voltage Fault 0x5112
Device Supply: Voltage Under-Run U3 0x5113
Device Supply: Voltage Under-Run U4 0x5114
Device Supply: Voltage Under-Run U5 0x5115
Device Supply: Voltage Under-Run U6 0x5116
Device Supply: Voltage Under-Run U7 0x5117
Device Supply: Voltage Under-Run U8 0x5118
Device Supply: Voltage Under-Run U9 0x5119
Device Supply: Short Circuit 0x5151
Device Supply: Error In Periphery 0x5160
Device Controller: General Error 0x5200
Device Control Section: General Error 0x5300
Device Power Section: General Error 0x5400
Device Power Section: Error In Output Driver 0x5410
Device Power Section: Fuse Blown/Open 0x5450
Device Power Section: Fuse Blown/Open S1 0x5451
Device Power Section: Fuse Blown/Open S2 0x5452
Device Power Section: Fuse Blown/Open S3 0x5453
Device Power Section: Fuse Blown/Open S4 0x5454
Device Power Section: Fuse Blown/Open S5 0x5455
Device Power Section: Fuse Blown/Open S6 0x5456
Device Power Section: Fuse Blown/Open S7 0x5457
Device Power Section: Fuse Blown/Open S8 0x5458
Device Power Section: Fuse Blown/Open S9 0x5459
Error In Additional Device Communication 0x5500
Error In Device Communication Interface 2 0x5510
table continued on next page