EasyManua.ls Logo

Basler BE1-11g - Page 393

Basler BE1-11g
672 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9424200994 Rev N 381
Step 10: (Optional.) Repeat steps 1 through 9 for the B-phase and C-phase voltage inputs.
Step 11: (Optional.) Repeat steps 1 through 10 for settings group 1, 2, and 3.
Step 12: Use BESTCOMSPlus to open the Protection, Voltage, Overexcitation (24) screen and send the
test settings in Table 127 to the BE1-11g.
Table 127. Definite Time Pickup Test Settings
Setting
Value
Description
Inverse Time Pickup
0
Disables Inverse Time Pickup
Definite Timer 1 Pickup
2.36
Sets Definite Timer 1 Pickup at 118% of nominal (2.36 V/Hz)
Definite Timer 1 Time Delay
50
Sets Definite Timer 1 Time Delay at 50 ms (minimum)
Definite Timer 2 Pickup
0
Disables Definite Timer 2 Pickup
Alarm Pickup
0
Disables Alarm Pickup
Step 13: Prepare to monitor the operation of the Definite Timer 1 Pickup. Pickup operation can be
verified by monitoring OUT2. Operation of the Definite Timer 1 Trip can be verified by
monitoring OUT1.
Step 14: Connect a three-phase, 100 Vac/50-Hz or 120 Vac/60-hertz voltage source (depending on
user's nominal frequency) to Terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and
C16 (neutral).
Step 15: Apply A-phase voltage at nominal frequency and slowly increase until OUT2 closes (V/H Trip x
Freq = PU) and record the pickup. Verify that there is a 24 target on the front-panel display.
Slowly decrease the A-phase voltage until OUT2 opens and record the dropout.
Step 16: (Optional.) Repeat steps 12 through 15 for higher and lower pickup settings.
Step 17: (Optional.) Repeat steps 12 through 16 for frequencies other than nominal.
Step 18: (Optional.) Repeat steps 12 through 17 for the B-phase and C-phase voltage inputs.
Step 19: (Optional.) Repeat steps 12 through 18 for settings group 1, 2, and 3.
Step 20: (Optional.) Set Definite Timer 1 Pickup to 0 and Definite Timer 2 Pickup to 2.36 V/Hz and repeat
steps 12 through 19 for Definite Timer 2 Pickup.
Inverse Time Verification
The following test uses the (M-1)^2 time curve.
Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Overexcitation (24) screen and send the
test settings in Table 128 to the BE1-11g.
Table 128. Inverse Time Verification Test Settings
Setting
Value
Description
Inverse Time Pickup
2.1
Sets Inverse Time Pickup at 105% of nominal (2.10 V/Hz)
Inverse Time Dial
0.5
Sets Inverse Time Dial at 0.5
Inverse Reset Dial
0
Sets Inverse Reset Dial at minimum
Curve Exponent
2
Sets Curve Exponent to 2
Definite Timer 1 Pickup
0
Disables Definite Timer 1 Pickup
Definite Timer 2 Pickup
0
Disables Definite Timer 2 Pickup
Alarm Pickup
0
Disables Alarm Pickup
Step 2: Connect and apply 120 Vac, three-phase, 60-hertz voltage source to Terminals C13 (A-phase),
C14 (B-phase), C15 (C-phase), and C16 (neutral).
BE1-11g Overexcitation (24) Test

Table of Contents

Related product manuals