5-6 DGC-2020 BESTlogic+ Programmable 9400200990 Rev I
Name Description Symbol
Engine KW Over
Load 1
TRUE when the Engine KW Overload 1 Pre-Alarm
settings have been exceeded.
Engine KW Over
Load 2
TRUE when the Engine KW Overload 2 Pre-Alarm
settings have been exceeded.
Engine KW Over
Load 3
TRUE when the Engine KW Overload 3 Pre-Alarm
settings have been exceeded.
Fuel Leak
TRUE when the Fuel Leak Detect function is configured
as a Pre-Alarm and the activation delay has expired.
Fuel Level Sender
Fail
TRUE when the Fuel Level Sender Fail is configured as
a Pre-Alarm and the activation delay has expired.
Global Pre-Alarm TRUE when one or more Pre-Alarms are set.
Hi Coolant Temp
TRUE when the High Coolant Temp Pre-Alarm threshold
has been exceeded.
High Fuel Level
TRUE when the High Fuel Level Pre-Alarm settings
have been exceeded.
Intergenset Comm
Fail
TRUE when an individual generator detects that it had
been connected to a generator network, but has lost the
connection.
Load Share
Module Comm Fail
TRUE when communication from the LSM-2020 to the
DGC-2020 has been lost.
Low Battery
Voltage
TRUE when the Low Battery Voltage Pre-Alarm settings
have been exceeded.
Low Coolant Level
TRUE when the Low Coolant Level function is
configured as a Pre-Alarm and the activation delay has
expired. In addition, TRUE when Canbus is enabled and
the Low Coolant Level Pre-Alarm threshold has been
exceeded.
Low Coolant Temp
TRUE when the Low Coolant Temp Pre-Alarm threshold
has been exceeded.
Low Fuel Level
TRUE when the Low Fuel Level Pre-Alarm threshold has
been exceeded.
Low Oil Pressure
TRUE when the Low Oil Pressure Pre-Alarm threshold
has been exceeded.
Maintenance
Interval
TRUE when the Maintenance Interval Pre-Alarm
threshold has been exceeded.
MPU Fail TRUE when the MPU has failed.
Multiple Contact
Expansion
Modules Detected
TRUE when more than one CEM-2020 is connected.
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler DGC-2020 and is the answer not in the manual?

Basler DGC-2020 Specifications

General IconGeneral
BrandBasler
ModelDGC-2020
CategoryController
LanguageEnglish

Related product manuals