Baumer Description | 3
V2 | OX100 Operating Manual 23
3.3.2 IO-Link
The sensor supports IO-Link communication for transfer of cyclic process data and status infor-
mation. The device supports COM 3 transmission rate in line with IO-Link specification.
You can either use the setup parameters stored in the sensor or the web interface-programmed
setup parameters (see Mode Save Parameter-Setups [}62]). Further parametrisation of mea-
surement-relevant parameters via IO-Link is not possible. The order of the measured results is
defined by the order specified in the web interface (see Mode Measurement Tools Parametriza-
tion [}54]).
Cyclic/acyclic data
During data transfer, a distinction is made between cyclic data and acyclic data:
n
Cyclic data: The measured values 1 to 5 parameterized via the web interface, the encoder
position (if encoder input present) and the following binary signals will be transferred as
cyclical data:
▪ Alarm output
▪ Quality bit (signals a weak signal)
▪ Switching states of the switching outputs
▪ Status information whether the sensor is currently in the parametrisation mode.
▪ Information whether the time has been synchronised.
n
Acyclic data: The measured values 1 to 7 parameterized via the web interface, the sen-
sor's measurement rate and all other available information (see IODD file) are transferred as
acyclic data.