Trouble shooting 8.5T
P SUError (Error in the module Power input) P0205
Error
no.
Mea ning Reaction Troubleshooting
65–77 Not assigned
78 Offset of current channels outside the
limits
PI Contact Baumüller.
79 Overcurrent was measured (SW) PI Reduce the load and check the current
controller settings a s well as the
cabling and the motor
AmpError (Error in module Power unit) P0206
Error
no.
Mea ning Reaction Troubleshooting
80 Not assigned
81 Temperature threshold of heatsink
exceeded
PI Let the device cool down and/or
reduce the load.
82 Overvoltage DC link (UDC link) PI Reduce the DC link voltage.
83 Reduce overcurrent in the power unit PI Reduce the load and check the current
controller settings a s well as the
cabling and the motor.
84 Not assigned
85 Temperature threshold of inside a ir
exceeded
PI Make sure of a sufficient ventilation in
the device.
86 Not assigned
87 Error/defective safety relay PI Check the function of the safety relay.
88–94 Not assigned
95 Chopper transistor overloaded PI Reduce the brake current or use an
external chopper resistor.