D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 35
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Test Reports
Sending Test Reports
Automatic: To send a single Test Report (R# Test Report) automatically, enable Sked
Function Code #9 (Test Report) in the Skeds section of the program. Refer to
Section Table 3.9 Test Reports, page 36.
Manual: To send a single Test Report manually, enter [COMMAND][4][1] at the keypad. Refer
to Section Send Report, page 96.
To expand this Test Report to include any off-normal point condition or other off-normal
system conditions, Expand Test Report (Section Expand Test Report, page 23) must be
programmed Yes. Refer to the footnotes with Table 3.10, Page 37 for a list of event types that
are included in an expanded test report. Additionally, the expanded test report includes
Summary Fire Supervisory, Summary Fire Fault, Summary Controlled Point Fault, and
Summary Point Device Fault conditions.
The control panel can generate an Expanded Off- Normal Test Report by using Sked Function
Code 28 or a Non-Expanded Off-Normal Test Report using Sked Function Code 29. To
generate this event, one or more points must be in an off-normal state at the time the Sked
executes. Expanded Off-Normal Test Reports include the Off Normal Test Report Event as well
as a panel-wide summary of off-normal point and system conditions. Non-Expanded Off-
Normal Test Report Events are sent only when a point is in the off normal state but sends only
the Off-Normal Test Report Event.
Sending Status Reports
Automatic: To send a Status Report automatically that includes the events shown in the
footnotes in Table 3.9, Page 36, enable Sked Function Code #10 in the Skeds section of the
program.
Manual: To send a Status Report manually that includes the events shown in the footnotes in
Table 3.9, Page 36, enter [COMMAND][4][2] at the keypad. Refer to Section View Memory,
page 96.
Sending off-normal conditions as a Status Report following a Test Report is required by some
automation systems. Sending off-normal conditions as a Non-status Report that follows a Test
Report is required for other automation systems.
An off-normal condition is any point that is missing, trouble, supervisory, or in alarm. Also,
points not cleared at the keypad report as off-normal.
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), enable Test Reports.