Commissioning
3
ekr CON 600 net – Process Data Exchange via Profibus 21/79
3.2.1 Calling up the Configuration Menu
The symbol for the Profibus configuration menu is only
displayed in the Setup menu if the controller has detected
an integrated Profibus interface module.
Carry out the following steps to call up the Profibus configuration
menu on the ekrCON600net controller:
1. Press the Manual mode key.
The LED of the key illuminates.
The controller switches to manual mode.
2. Press the SETUP key.
The controller changes to setup mode.
The first page of the setup menu appears in the display of the
ekrcommander control panel.
3. To call up the next page of the setup menu, tap the right arrow
button in the display.
The second page of the setup menu appears in the display.
4. Press the adjoining button to activate the Profibus configuration
menu.
The Profibus configuration menu appears in the display.