Communication Objects
4
ekr CON 600 net – Process Data Exchange via Profibus 27/79
4.1.2 Description of the Communication Objects
4.1.2.1 EkrIn_HEADER Data
Slot 1
Slot Name ADI_Data_1_1
Object EkrIn_HEADER Data
Function Setting the operating mode, Setting the guiding mode,
Activating the watchdog function,
Switching on the oscillation function for the web of material
Data types Unsigned8, Unsigned16, Unsigned32
Access Write-only
Object length 12 bytes
Name Data Type Bit Meaning Data Description
Little
Endian
Big
Endian
Parameter
selection bit
field
Unsigned8
0 0 Protocol number The following data becomes valid if the
corresponding bit in this parameter
selection bit field is set (see Using the
Parameter Selection Bit Field, page 17).
1 1 Control bit field 1
2 2 Control bit field 2
Padding byte Unsigned8 Padding byte Unusable
Protocol Unsigned16 Reserved
Control bit
field 1
Unsigned32
0
…
3
24
…
27
Reserved Do not use. Always 0.
4 28 Operating mode 1_4
0h: No change
1h: Reserved
2h: Reserved
3h:
– Manual mode
4h:
– Automatic mode
5h:
– Center positioning
6h: Reserved
7h: Reserved
5 29 Operating mode 2_4
6 30 Operating mode 3_4
7 31 Operating mode 4_4
8 16 Guiding mode 1_4
0h: No change
1h:
– Web edge guiding – Edge1
2h:
– Web edge guiding – Edge2
3h:
– Line/contrast guiding
4h: Reserved
5h:
– Web center-line guiding –
Center1&2
6h:
– Watchdog edge1
7h:
– Watchdog edge2
9 17 Guiding mode 2_4
10 18 Guiding mode 3_4
11 19 Guiding mode 4_4