EasyManuals Logo

Buderus Logamatic 4323 Service Instructions

Buderus Logamatic 4323
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
Fault
20
Logamatic 4323 - Subject to technical modifications.
106
Remote
control x
Because no actual room
temperature is available, the
effects of the following features
are disabled: Room influence,
start and stop optimisation,
automatic adaptation.
Remote control incorrectly
connected or faulty.
Check remote control function
or connection.
Replace remote control or module.
Incorrect address allocated to
remote control.
– Check remote control address
(see BFU remote control
documentation).
Remote control cable damaged by
a drill or is broken.
Check connecting cables.
Communi-
cation HKx
Because no actual room
temperature is available, the
effects of the following features
are disabled: Room influence,
start and stop optimisation,
automatic adaptation.
Remote control incorrectly
connected or faulty.
Check remote control function or
connection.
By mistake, neither a BFU remote
control nor a MEC2 was selected
for this heating circuit in the MEC2.
Select the correct remote control in
the MEC2 under "Remote control"
(Æ Chapter 11.7).
Incorrect address allocated to
remote control.
Check remote control address (see
BFU remote control
documentation).
Remote control or matching
module is faulty.
Replace remote control or module.
ECOCAN-BUS
reception
No effect on the control
characteristics.
Rotary encoder on CM431 (behind
MEC2 or boiler display) incorrectly
addressed.
Check setting of rotary encoder
(Æ Chapter 5.1).
Gravity switch on NM482 is
incorrectly positioned.
Check gravity switch
(Æ Chapter 5.2).
No master
The system operates with
minimum outside temperature.
By mistake, there is no master
control unit (address 1) in the
network.
Check addresses of all control
units in the network.
On the master control unit, CM431
must be set to address 1
(Æ Chapter 5.1).
Connecting cable to master control
unit is interrupted.
Check function of connecting
cable.
Master control unit (address 1) is
switched off or faulty.
Check master control unit and
replace if necessary.
Conflicting Bus
addresses
Bus communication no longer
possible.
All control functions requiring data
exchange via the ECOCAN-BUS
can no longer be implemented.
Multiple identical addresses are
present.
Each address must only be
assigned once in the ECOCAN-
BUS network.
Check the addresses of all Bus
subscribers (address settings
Æ Chapter 5.1).
Address
conflict x
Functions of the module with
address conflict can no longer be
implemented. All other modules in
the control unit as well as the
ECOCAN-BUS continue to
function normally.
Module must not be installed into
this control unit (e.g. 2 x FM441 in
one control unit or FM447 in
Logamatic 4323).
Check using Chapter 5, Tab. 1,
whether the module may be used
for this type of control unit.
Incorrect
Module x
Module switches all outputs off
and corresponding fault LED on.
A different module was installed in
one slot of the control unit (e.g.
FM442 was replaced with FM441).
Insert new module into MEC2
(Æ Chapter 10).
By mistake, an incorrect module
was selected for this MEC2 slot.
Check module selected in MEC2
(Æ Chapter 10).
MEC2 programming unit,
corresponding module or control
unit is faulty.
If necessary, replace relevant
component.
Fault Effect on control
characteristics
Possible causes of the fault Remedy
Tab. 4 Fault table

Table of Contents

Other manuals for Buderus Logamatic 4323

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic 4323 and is the answer not in the manual?

Buderus Logamatic 4323 Specifications

General IconGeneral
BrandBuderus
ModelLogamatic 4323
CategoryControl Unit
LanguageEnglish

Related product manuals