12.5 Setting hysteresis
With the "Hysteresis" function, you can determine at how many Kelvin (K)
below
the set DHW temperature the reheating of the cylinder begins.
(1 K equates to 1 °C)
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "DHW" appears.
Press "Display" to call up a submenu (here: "DHW").
The display shows the selected submenu.
Turn the rotary selector until submenu "Hysteresis" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "-20K").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
DHW DATA
yes
DHW
DHW DATA
-5K
Hysteresis
+
DHW DATA
-20K
Hysteresis
Input range Factory setting
Hysteresis
-20 K2 K -5 K