Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
51
11.9 Select the type of setback
You can select the following functions for setback or night operation:
"Hold if cold" determines the outside temperature limit.
The heating circuit is switched off when this value is exceeded.
Below this limit, the heating system heats to the set night temperature.
With "Hold room temp" you determine a night temperature as room
temperature.
The heating circuit is switched off when this value is exceeded.
Below this limit, the heating system heats to the set night temperature.
For this function a remote control must be located in the relevant room.
In setback mode, the heating circuit is generally switched off at "Standby".
In setback mode, the system heats to the set night temperature if "Reduced"
is selected. The heating circuit pumps operate constantly.
Setting the heating system to "Room controller" and setback type to "Reduced"
achieves the same effect for temperature setback as "Hold room temp".
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here:
"Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
USER INFORMATION
You can only select "Reduced", "Hold if cold" or "Standby" if you have selected
"Constant" under the main parameter "Heating system".
+
+
HEAT CIRC. DATA 2
Radiators
Heating system

Table of Contents

Other manuals for Buderus Logamatic 4323

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic 4323 and is the answer not in the manual?

Buderus Logamatic 4323 Specifications

General IconGeneral
BrandBuderus
ModelLogamatic 4323
CategoryControl Unit
LanguageEnglish

Related product manuals