Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
53
11.10Setting the outside stop temperature
Enter the outside temperature at which the heating operation should change
over from "Standby" to "Reduced", if you have selected "Hold if cold" as setback
type.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here:
"Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "Outside hold frm" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "1°C").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
HEAT CIRC. DATA 2
Radiators
Heating system
HEAT CIRC. DATA 2
5°C
Outside hold frm
+
HEAT CIRC. DATA 2
1°C
Outside hold frm
Input range Factory setting
Outside hold frm
-20 °C10 °C 5 °C