11.19Setting the DHW priority
The circulation pumps of all heating circuits are switched off whilst DHW
is
being heated if you activate the function "DHW priority".
In mixed heating circuits, the mixer is moved towards "Mixer closes" (colder).
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here:
"Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "DHW priority" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "no").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+