DHW data
12
Logamatic 4323 - Subject to technical modifications.
80
12.6 Raising the boiler water temperature
With the "Boiler raising" function, you can determine the boiler water
temperature during DHW heating.
The boiler raising temperature is added to the required DHW temperature
and
results in the required flow temperature for DHW heating.
The factory setting of 40 K (1 K equals 1 °C) is optimised for rapid DHW heating.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "DHW" appears.
Press "Display" to call up a submenu (here: "DHW").
The display shows the selected submenu.
Turn the rotary selector until submenu "Boiler raising" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "10K").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
DHW DATA
yes
DHW
DHW DATA
40K
Boiler raising
+
DHW DATA
10K
Boiler raising
Input range Factory setting
Boiler raising
10 K40 K 40 K