Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
47
11.6 Maximum flow temperature
The maximum flow temperature limits the heating curve to a maximum set value.
This function will not be displayed with "Constant" heating systems.
Change value only if necessary.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here:
"Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "Maximum Flow temp." appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "60°C"). This value sets the temperature above which the flow
temperature must not rise.
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
HEAT CIRC. DATA 2
Radiators
Heating system
HEAT CIRC. DATA 2
75°C
Flow temp.
Maximum
+
HEAT CIRC. DATA 2
60°C
Flow temp.
Maximum
Input range Factory setting
Maximum flow temperature for underfloor
heating
30 °C60 °C 50 °C
Maximum flow temperature for radiators,
convector heaters, low end
30 °C90 °C 75 °C