DHW data
12
Logamatic 4323 - Subject to technical modifications.
88
12.13Daily heat-up
When daily heat-up is set, the DHW (which may include a solar cylinder,
if
installed) is heated to 60 °C once a day to prevent legionella bacteria from
multiplying in the DHW. This complies with the requirements of DVGW Code
of
Practice W551.
The time when the cylinder is heated can be adjusted.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "DHW" appears.
Press "Display" to call up a submenu (here: "DHW").
The display shows the selected submenu.
Turn the rotary selector until "Daily heat-up" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "18:00").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
DHW DATA
yes
DHW
DHW DATA
disabled
heat-up
Daily
+
DHW DATA
18:00
heat-up
Daily
USER INFORMATION
If the DHW was heated to 60 °C within the last 12 hours, it is not heated
at
the specified time.
Input range Factory setting
Daily heat-up
disabled
00:00
23:00
disabled

Table of Contents

Other manuals for Buderus Logamatic 4323

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic 4323 and is the answer not in the manual?

Buderus Logamatic 4323 Specifications

General IconGeneral
BrandBuderus
ModelLogamatic 4323
CategoryControl Unit
LanguageEnglish

Related product manuals