Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
41
11 Heating circuit data
You may select the following heating systems:
None
The heating circuit function is not required. All subsequent submenu points
relating to "Heat circ. data" no longer apply.
Radiators or Convector
The heating curve is automatically calculated for radiators or convector
heaters, depending on the required curve.
Underfloor
A flatter heating curve is automatically calculated for lower design
temperatures.
Low end
The level of the flow temperature is a linear consequence of the outside
temperature. The resulting heating curve connects as a straight line the low
end with a second point that depends on the design temperature.
Constant
Use this system for controlling a swimming pool heating system or to pre-
control ventilation circuits, if the heating must always provide the same, set
flow temperature, independent of the outside temperature. You cannot install
a remote control for this heating circuit if you have selected this system.
Room controller
The set flow temperature is only dependent on the actual room temperature.
For this, you must install a remote control inside the room. The heating
system is switched off if the room becomes too hot.