Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
55
11.12Stopping setback at low outside temperatures
DIN 12831 enables the stopping of setback when the actual temperature falls
below a selected adjusted outside temperature, to prevent the living space
cooling down excessively.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here:
"Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "No setback Below outside temp."
appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "0°C").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
USER INFORMATION
Setback will not be blocked in manual mode or in holiday mode.
+
+
HEAT CIRC. DATA 2
Radiators
Heating system
HEAT CIRC. DATA 2
disabled
Below outside temp.
No setback
+
HEAT CIRC. DATA 2
0°C
Below outside temp.
No setback
Input range Factory setting
No setback
Below outside temp.
disabled
-30 °C
10 °C
disabled

Table of Contents

Other manuals for Buderus Logamatic 4323

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic 4323 and is the answer not in the manual?

Buderus Logamatic 4323 Specifications

General IconGeneral
BrandBuderus
ModelLogamatic 4323
CategoryControl Unit
LanguageEnglish

Related product manuals