General parameters
9
Logamatic 4323 - Subject to technical modifications.
30
9.2 Type of building
Under building type, please enter the heat storage capacity of the building.
Different types of construction have different heat storage capacities.
This
function sets the heating system to the specified construction type.
The heat storage capacity is divided into three categories:
Call up the service level. "Gen. parameters" is shown as the first main menu.
Press "Display" to call up a submenu (here: "Min outside temp").
The display shows the selected submenu.
Turn the rotary selector until submenu "Type of building" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "heavy").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
light = low heat storage capacity, e.g. pre-fabricated houses,
wooden-framed constructions,
medium = medium heat storage capacity, e.g. house built with breeze blocks,
heavy = high heat storage capacity, e.g. house built with bricks.