DHW data
12
Logamatic 4323 - Subject to technical modifications.
83
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
12.9 Selecting and setting up thermal disinfection
If you select the "Therm. disinfect" function, the DHW is brought to a temperature
(70 °C) once or several times a week. This is high enough to kill off germs
(e.g.
legionella bacteria).
The cylinder primary pump and DHW circulation pump run constantly during the
thermal disinfection process.
If you have selected "Therm. disinfect yes", thermal disinfection commences
according to factory settings or your own preferences.
Thermal disinfection is indicated by LED on the FM441 module.
You may adjust the factory settings for thermal disinfection via additional menus.
The system tries to reach the set thermal disinfection temperature for three
hours. If
this fails, the fault message "Therm. disinfect failed" appears.
You may also set up thermal disinfection via your own switching program.
Input range Factory setting
External contact
Heating once
Therm. disinfect
none
none
USER INFORMATION
The "Therm. disinfect" function will not be displayed if thermal disinfection
was
previously selected via the "external contact WF 1/3" function.