DHW data
12
Logamatic 4323 - Subject to technical modifications.
90
12.15Setting the DHW circulation pump intervals
You can reduce operating costs using the intermittent DHW circulation pump
operation.
You can set DHW to be immediately available at the draw-off points,
using
the "DHW circulation per hour" function.
The set interval applies during the time when the time program enables
the
DHW circulation pump. This may be:
The factory-set DHW circulation pump program
Your own DHW circulation pump program
A connection to the heating circuit switching times
In constant operation the DHW circulation pump operates all day and is switched
off during night operation.
Example:
Your own time program was created that starts the DHW circulation pump
between 05:30
22:00 with setting "DHW circulation per hour 2 times ON".
The DHW circulation pump is switched on in cycles
at 05:30 for 3 minutes,
at 06:00 for 3 minutes,
at 06:30 for 3 minutes,
etc. until 22:00.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "DHW" appears.
Press "Display" to call up a submenu (here: "DHW").
The display shows the selected submenu.
Turn the rotary selector until submenu "DHW circulation per hour" appears.
The display shows the selected submenu.
+
+
DHW DATA
yes
DHW
DHW DATA
2 times on
per hour
DHW circulation

Table of Contents

Other manuals for Buderus Logamatic 4323

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic 4323 and is the answer not in the manual?

Buderus Logamatic 4323 Specifications

General IconGeneral
BrandBuderus
ModelLogamatic 4323
CategoryControl Unit
LanguageEnglish

Related product manuals