Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
61
11.17Setting stop optimisation time
If you have selected "Stop" or "Start/Stop" in section 11.16, you may
enter as of when the setback operation should begin. Change the setting only
if
necessary.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here:
"Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "Shutdown optimisation time" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "30 min").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
Input range Factory setting
Shutdown optimisation time
10 minutes – 60 minutes 60 minutes