3–25 62-11785
• RESTART
TEMP:
0.5 to 18°F (.28 to 10°C)
(in 0.5° increments)
5.4°F (3°C)
Following the Minimum Off Time, should a compartment tem-
perature drift this far above or below setpoint in the Perishable
Range or above setpoint in the Frozen Range, the unit will re-
start.
• OVERRIDE
TEMP:
3.6 to 18°F (2 to10°C) (in
0.5 degree increments)
12.0°F (6.7°C)
This selects the override temperature for the Minimum Off Time
portion of the Auto Start-Stop Off Cycle. During the Minimum
Off Time, should the refrigerated compartment temperature
drift this far above or below setpoint in the Perishable Range,
or above setpoint in the Frozen Range, the unit will override the
Minimum Off Time, and restart.
• MAX OFF
TIME:
OFF
10MINS
TO
255MINS (in 1 minute in-
crements)
OFF - There is no maximum off time.
When a minute value is selected, this is the longest amount of
time the unit will remain off during a (Perishable or Frozen or
both) Auto Start/Stop Off Cycle. When this time expires, the unit
will restart and run for the Minimum Run Time, regardless of
any temperature change inside the compartment.
•FROZEN
SHUTDOWN
OFFSET:
0°F to 1.1°F
(0°C to 0.6°C) (in 0.1°F
or C increments)
This only applies to Frozen Setpoints in Start-Stop operation.
This offset is the number of degrees below setpoint that the unit
will run before cycling off. This will allow for a lower average
compartment temperature when considering temperature rises
during off cycles.
OVERRIDES
OVERRIDE DOOR
SWITCH SHUTDOWN
(DS)
AND
OVERRIDE REMOTE
SWITCH 1 SHUT-
DOWN (REMS1)
AND
OVERRIDE REMOTE
SWITCH 2 SHUT-
DOWN (REMS2)
NO
YES
If the switches are all configured “Switch Not Installed”, this pa-
rameter will not display.
NO = the system will respond to the switch as configured.
YES = the configured action on activation of the switch will be
overridden and the action will be alarm only. The purpose of
this setting is to temporarily override the Configuration setting
in situations where shutdown is not desired.
VIEWING PREFERENCES
DISPLAY
TEMPERATURE
IN
°F
°C
Temperatures will display in either Fahrenheit (°F) or Celsius
(°C). (for North American Units, this function may be locked)
DISPLAY
PRESSURE IN
PSIG
BAR
Pressure will display in either psig or (bar).
(for North American Units, this function may be locked)
DATE FORMAT MM/DD/YYYY
DD/MM/YYYY
YES = In the Driver Mode, the alarm code and alarm descrip-
tion will be displayed.
ALARM
DESCRIPTIONS
YES
NO
NO = In the Driver Mode, only the alarm code will be displayed.
CONTRAST 0 TO 63 (In single
digit increments)
35
Higher numbers increase the contrast of the display screen.
Table 3–2 Functional Parameters
FUNCTION
PARAMETER
SELECTIONS
DESCRIPTION