Table 73 (Continuation): Modbus memory map (Table 1)
Parameter Symbol Instantaneous Maximum Minimum Units
Three-phase Cos φ Cos φ III 3A-3B 140-141 19E-19F x100
L1 Frequency Hz 3C-3D 142-143 1A0-1A1 Hz x100
L1-L2 Voltage V12 3E-3F 144-145 1A2-1A3 V x 10
L2-L3 Voltage V23 40-41 146-147 1A4-1A5 V x 10
L3-L1 Voltage V31 42-43 148-149 1A6-1A7 V x 10
Neutral Current N A N 44-45 14A-14B 1A8-1A9 mA
L1 voltage % THD %THDV1 46-47 14C-14D 1AA-1AB % x 10
L2 voltage % THD %THDV2 48-49 14E-14F 1AC-1AD % x 10
L3 voltage % THD %THDV3 4A-4B 150-151 1AE-1AF % x 10
L1 current % THD %THDI1 4C-4D 152-153 1B0-1B1 % x 10
L2 current % THD %THDI2 4E-4F 154-155 1B2-1B3 % x 10
L3 current % THD %THDI3 50-51 156-157 1B4-1B5 % x 10
Maximum demand kW III Md (Pd) 52-53 158-159 - W
Maximum demand kVA III Md (Pd) 54-55 15A-15B - VA
Maximum demand I AVG Md (Pd) 56-57 15C-15D - mA
Maximum demand I L1 Md (Pd) 58-59 15E-15F - mA
Maximum demand I L2 Md (Pd) 5A-5B 160-161 - mA
Maximum demand I L3 Md (Pd) 5C-5D 162-163 - mA
Maximum demand kvarL III kvarL 200-201 204-205 - kvarL
Maximum demand kvarC III kvarC 202-203 206-207 - kvarC
8.3.2.- ENERGY VARIABLES
For these variables is implemented the Function 0x03 and 0x04.
Table 74: Modbus memory map (Table 2)
Parameter Symbol Tariff 1 Tariff 2 Tariff 3 Total Units
Consumed active energy kW) kWh III 5E-5F 88-89 B2-B3 DC-DD kWh
Consumed active energy (W) kWh III 60-61 8A-8B B4-B5 DE-DF Wh
Consumed inductive reactive energy (kvarhL) kvarhL III 62-63 8C-8D B6-B7 E0-E1 kvarh
Consumed inductive reactive energy (varhL) kvarhL III 64-65 8E-8F B8-B9 E2-E3 varh
Consumed capacitive reactive energy (kvarhC) kvarhC III 66-67 90-91 BA-BB E4-E5 kvarh
Consumed capacitive reactive energy (varhC) kvarhC III 68-69 92-93 BC-BD E6-E7 varh
Consumed apparent energy (kVAh) kVAh III 6A-6B 94-95 BE-BF E8-E9 kVAh
Consumed apparent energy (VAh) kVAh III 6C-6D 96-97 C0-C1 EA-EB VAh
Consumed CO
2
emissions KgCO
2
6E-6F 98-99 C2-C3 EC-ED x10
Consumption cost $ 70-71 9A-9B C4-C5 EE-EF x10
Generated active energy (kW) kWh III 72-73 9C-9D C6-C7 F0-F1 kWh
Generated active energy (W) kWh III 74-75 9E-9F C8-C9 F2-F3 Wh
Generated inductive reactive energy (kvarhL) kvarhL III 76-77 A0-A1 CA-CB F4-F5 kvarh
Generated inductive reactive energy (varhL) kvarhL III 78-79 A2-A3 CC-CD F6-F7 varh
Generated capacitive reactive energy (kvarhC) kvarhC III 7A-7B A4-A5 CE-CF F8-F9 kvarh
Generated capacitive reactive energy (varhC) kvarhC III 7C-7D A6-A7 D0-D1 FA-FB varh
Generated apparent energy (kVAh) kVAh III 7E-7F A8-A9 D2-D3 FC-FD kVAh
Generated apparent energy (VAh) kVAh III 80-81 AA-AB D4-D5 FE-EF VAh