Press key   for 3 seconds to edit the value. The   icon appears at the top of the screen. 
The key   jumps between the possible options. 
To validate the data, press   for 3 seconds and the   icon will disappear from the display.
Configuration values
Table 31:Configuration values:  Type of integration of the maximum demand.
Type of integration of the maximum demand
Possible values
SIide Sliding window
timed Fixed window
Note: When modifying the type of integration, the device restarts the calculation of the maximum 
demand.
Press key   to access the next programming step.
 6.11.- MAXIMUM DEMAND INTEGRATION PERIOD
The maximum demand integration period is programmed in minutes on this screen. See “4.1.2.- 
MAXIMUM DEMAND”.
Press key   for 3 seconds to edit the value. The   icon appears at the top of the screen.
To enter or modify the value, press the   key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key   to 
modify the other values.
To validate the data, press   for 3 seconds and the   icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum programming 
value.
Configuration values
Table 32:Configuration values: Maximum demand integration period.
Maximum demand integration period
Minimum value 0
Maximum value 60
64
CVM-C11
Instruction Manual