6.9.- TYPE OF INSTALLATION
The type of installation is selected on this screen.
Press key   for 3 seconds to edit the value. The   icon appears at the top of the screen.
The key   jumps between the possible options.
To validate the data, press   for 3 seconds and the   icon will disappear from the display.
Configuration values
Table 30:Configuration values: Type of installation.
Type of installation
Possible 
values
4-3Ph Three-phase network measurement with a 4-wire connection. 
3-3Ph Three-phase network measurement with a 3-wire connection.
3-AroN Three-phase network measurement with a 3-wire connection and transformers 
with an ARON connection.
3-2Ph Two-phase network measurement with a 3-wire connection.
 2-2Ph Single-phase network measurement, phase to phase, with a 2-wire connection.
2-1Ph Single-phase network measurement, phase to neutral, with a 2-wire connection.
3-3IT Measuring Three-Phase Networks with a 3-wire and earth connection
(7)
(7)
  Installation available from version C11.1005.230119 of the device.
Press key   to access the next programming step.
 
 6.10.- TYPE OF INTEGRATION OF THE MAXIMUM DEMAND
In this screen, the type of integration to be used for the calculation of the maximum demand is 
selected. See “4.1.2.- MAXIMUM DEMAND”.