4. OPERATION
The CVM-C11 is a four-quadrant power analyzer (consumption and generation).
The device can operate according to three different measurement conventions:
CIRCUTOR measurement convention.
IEC 61557-12 measurement convention.
IEEE 1459 measurement convention.
The measurement convention is configured in the setup menu, see “6.8.- MEASUREMENT CONVENTION”.
CIRCUTOR measurement convention:
90º
180º
-90º
Capacitive
Capacitive
Inductive
Inductive
Generation
Power
Consumption
Power
Single-phaseThree-phase
Single-phase
Single-phase
Single-phase
Three-phase
Three-phase
Three-phase
k
k
k
k
k
k
k
k
k
k
k
k
k
k
k
k
k
k
k
k
Figure 25: CIRCUTOR measurement convention.
IEC 61557-12 measurement convention:
Q
P
Q1Q2
Q3
Q4
P < 0 Q > 0 PF < 0
Capacitive
Capacitive
Inductive
Inductive
P < 0 Q < 0 PF < 0 P > 0 Q < 0 PF > 0
P > 0 Q > 0 PF > 0
Operation in the 4 quadrants (Q1, Q2, Q3, Q4)
0 +
0 +
cos φ > 0
cos φ > 0
Q1
Q4
+ 1
+ 1
cos φ values in the receiver operating mode (Q1,Q4)
Figure 26: Convenio de medida IEC 61557-12.