6.23.- COST RATIO OF CONSUMED ENERGY
The cost per kWh of electricity of the three tariffs of the device is calculated on this screen.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
Press key to browse the different tariffs.
To validate the data, press for 3 seconds and the icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum programming
value.
Configuration values
Table 46:Configuration values: cost ratio, consumed energy.
Cost ratio, consumed energy
Minimum value 0
Maximum value 1.9999
Press key to access the next programming step.
6.24.- COST RATIO OF GENERATED ENERGY
The cost per kWh of electricity of the three tariffs of the device is calculated on this screen.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.