To access the first programming step, press the key.
The programming parameters are validated as follows:
When on reaching the last point on the programming menu (6.40.- LOCKING THE PROGRAM
MING”) the key is pressed .
At any point in the programming, by pressing the key for 3 seconds.
If the device is reset before validation or no key is pressed for 30 seconds, the configuration will not
be stored in the memory.
To exit the configuration menu, press the key for 3 seconds.
Note: In the annex ANNEX A. CONFIGURATION MENUS you can see the configuration tree.
6.1.- PRIMARY VOLTAGE
On this screen the voltage transformer primary is programmed.
Press key for 3 seconds to edit the transformer primary value. The icon appears at the top
of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
To validate the data, press for 3 seconds and the icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum programming
value.
Configuration values
Table 22:Configuration values: Primary voltage.
Primary voltage
Minimum value 1
Maximum value 599999
57
Instruction Manual
CVM-C11