Figure 36: Analyzer profile screen displaying the maximum values.
 
To see the minimum values of the screen being displayed, press the   key for 3 seconds. These are 
displayed for 30 seconds. The   symbol will be displayed.
The maximum and minimum values are reset on the programming menu. (“6.17.- DELETING MAXIMUM 
AND MINIMUM VALUES”).
5.1.2.- MAXIMUM DEMAND
 
The device calculates the maximum demand of the following: 
    Current L1, L2 y L3.
 The three-phase current.
  Three-Phase Active Power.
  Three-Phase Apparent Power.
  Three-Phase Inductive Reactive Power
  Three-Phase Capacitive Reactive Power
This value can be displayed on the display screen of the parameter by pressing the   and   
keys at the same time. 
The   symbol appears on the display (Figure 37).
Figure 37: Analyzer profile screen displaying the maximum demand values.
 
Press keys   or   to stop displaying the maximum demand values.
The maximum demand is programmed in the configuration menu from parameters “6.10.- TYPE OF 
INTEGRATION OF THE MAXIMUM DEMAND” y “6.11.- MAXIMUM DEMAND INTEGRATION PERIOD”.
The maximum demand values are reset on the programming menu: “6.12. DELETING MAXIMUM DE
MAND”.