6.25.1.- MAXIMUM VALUE
On this screen, the value above which the alarm is activated is programmed.
Press key   for 3 seconds to edit the value. The   icon appears at the top of the screen.
To enter or modify the value, press the   key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key   to 
modify the other values.
In the case of some parameters (Table 50), you can modify the position of the decimal point. To do so, 
press key   after modifying the last digit and the decimal point will start flashing.
Press key   repeatedly to modify the position of the decimal point.
When the decimal point is in the desired position, press the key   to end the programming, pressing 
now the key   we can set a positive or negative value.
Note: Pay special attention when programming the Generation Power (displayed with negative values).
Example: If you wish to enter a generation power alarm with limits between 2 kW and 1 kW, program 
the following as the maximum value : - 1 kW and the following as the minimum value : - 2 kW.
To validate the data, press   for 3 seconds and the   icon will disappear from the display.
Configuration values
Table 50: Decimal point and units of the alarm parameters.
Types of parameters Units Decimal point
Voltage 
2000 kV
200.0 kV
20.00 kV
2.000 kV
Programmable
Current A Programmable
Frequency Hz Fixed
Power  kW Programmable
Power factor PF Fixed
Cosine φ
φ
Fixed
Maximum current demand A Programmable
Maximum power demand kW Programmable
THD % Fixed