8.3.5.- POWER STATUS
The Function 0x04 is implemented for this variable.
This variable indicates the quadrant in which the device is operating.
Table 78: Modbus memory map: Power status
Power status
Variable  Address  Default value
Power status 7D1 -
The variable format is shown in Table 79:
Table 79: Variable format: Power status.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 1: Capacitive 1: Inductive 1: Generated 1: Consumed
8.3.6.- THE DEVICE’S SERIAL NUMBER
The Function 0x04 is implemented for this variable.
Table 80: Modbus memory map: Serial number.
The device’s serial number
Variable  Address Default value
Serial number 578 - 579 -
Modbus ID identifier 640 870
8.3.7.- DETECTION OF INCORRECT DIRECTION OF ROTATION 
The Function 0x04 is implemented for this variable.
This variable indicates whether an incorrect direction of rotation has been detected in the voltages.
Table 81: Modbus memory map: Detection of incorrect direction of rotation.
Detection of incorrect direction of rotation
Variable  Address Value
Detection of incorrect direction of rotation 7D5
0: No fault has been detected
1: Fault detected
8.3.8.- STATUS OF INPUTS AND OUTPUTS
 
The Function 0x01 is implemented for this variable.
Table 82: Modbus memory map: Status of the outputs.
Status of the outputs 
(9)
Variable  Address  Value
Alarm relay 1 0F 0: Disabled - 1: Enabled
Alarm relay 2 10 0: Disabled - 1: Enabled
Digital output 1 11 0: Disabled - 1: Enabled
Digital output 2 12 0: Disabled - 1: Enabled
105