Configuration values
Table 54:Configuration values: Disconnection delay.
Disconnection delay
Minimum value 0 seconds
Maximum value 9999 seconds
Press key to access the next programming step.
6.25.7.- CONTACT STATUS
The status of relay contacts is selected on this screen.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
The key jumps between the possible options.
To validate the data, press for 3 seconds and the icon will disappear from the display.
Configuration values
Table 55:Configuration values: Contact status.
Contact status
Possible values
NO Normally open contact.
NC Normally closed contact.
Press key to access the next programming step.
6.26.- PROGRAMMING THE ALARM RELAY 2
In this step, all the values corresponding to alarm relay 2 are programmed.
They are programmed as in the case of alarm relay 1, see “6.25.- PROGRAMMING THE ALARM RELAY 1”.