6.3.- PRIMARY CURRENT
Note: Parameter not available in model CVM-C11-FLEX-IN-485-ICT2.
The current transformer primary is programmed on this screen.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
To validate the data, press for 3 seconds and the icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum programming
value.
Configuration values
Table 24:Configuration values: Primary current.
Primary current
Minimum value 1
Maximum value 10000
Voltage ratio x Current ratio < 600000
Note: The ratio is the relation between the primary and the secondary.
Press key to access the next programming step.
6.4.- SECONDARY CURRENT (CVMC11ITFINxxxICT2 Model
On this screen the current transformer secondary is selected.