If you have selected a parameter from Table 56, the subsequent programming steps are:
6.27.1.- KILOWATTS PER PULSE
In this section, the kilowatts per pulse of digital output T1 are programmed.
Press key   for 3 seconds to edit the value. The   icon appears at the top of the screen.
To enter or modify the value, press the   key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key   to 
modify the other values.
The programmed value will be deleted if the entered value is higher than the maximum programming 
value.
To validate the data, press   for 3 seconds and the   icon will disappear from the display.
Configuration values
Table 57:Configuration values: Kilowatts per pulse.
Energy CO
2 
Emissions Cost No. of hours
Minimum value 000.000 kWh 00000.0 kWh 00000.0 kWh 00000.0 kWh
Maximum value 999.999 kWh 99999.9 kWh 99999.9 kWh 99999.9 kWh
Example: To program 500 Wh per pulse: 000.500
    To program 1.5 kWh per pulse: 001.500
Press key   to access the next programming step.
Note: The device generates a pulse following the following formula:
3600
(
) x (
1000
Pulse: 
) 
83
Instruction Manual
CVM-C11