6.27.- PROGRAMMING ALARM 3 DIGITAL OUTPUT T1
All values for digital output T1 are programmed on this screen.
The variable code is selected on this screen, depending on Table 48, Table 49 and Table 56, which will
control digital output T1.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
When you enter the code of a variable on the display, the symbols for that variable will be activated.
To validate the data, press for 3 seconds and the icon will disappear from the display.
Configuration values
Note: Set the value to 000 if you do not wish to program a variable.
Table 56: Parameter codes used to program digital outputs.
Parameter
Tariff
Code
Tariff
Code
Tariff
Code
Tariff
Code
Consumed Active Energy T1 49 T2 70 T3 91 total 112
Generated Active Energy T1 59 T2 80 T3 101 total 122
Consumed Inductive Reactive Energy T1 51 T2 72 T3 93 total 114
Generated Inductive Reactive Energy T1 61 T2 82 T3 103 total 124
Consumed Capacitive Reactive Energy T1 53 T2 74 T3 95 total 116
Generated Capacitive Reactive Energy T1 63 T2 84 T3 105 total 126
Consumed Apparent Energy T1 55 T2 76 T3 97 total 118
Generated Apparent Energy T1 65 T2 86 T3 107 total 128
Consumed CO
2
Emissions T1 56 T2 77 T3 98 total 119
Generated CO
2
Emissions T1 66 T2 87 T3 108 total 129
Consumption Cost T1 57 T2 78 T3 99 total 120
Generation Cost T1 67 T2 88 T3 109 total 130
No. of hours T1 68 T2 89 T3 110 total 131
If you have selected a parameter from Table 48 or Table 49 the subsequent programming steps are the
same as for alarm relay 1, see (“6.25.- PROGRAMMING THE ALARM RELAY 1”).