4.6.- DIGITAL INPUTS
The CVM-C11 has two digital inputs (terminals 9, 10 and 11 on Figure 1) programmable to function as
logic input, tariff selection (Figure 35) or to generate a synchronism pulse to calculate the maximum
demand.
If configured as a logic input, the device displays the status of that input. See “6.29.- OPERATING MODE
OF DIGITAL INPUT 1and “6.30.- OPERATING MODE OF DIGITAL INPUT 2”.
The selected tariff can be determined in accordance with the status of the inputs, as shown in Table 20.
Table 20: Selecting the tariff in accordance with the input status.
IN1, Input 1 IN2, Input 2
Tariff
Synchronism pulse Logic input Tariff selection Logic input Tariff selection
x x T1
x x T1
x 0 T1
x 0 T1
x 1 T3
x 1 T3
0 x T1
1 x T2
0 0 T1
0 1 T3
1 0 T2
1 1 T1
4.7.- DIGITAL OUTPUTS
The CVM-C11 has two NPN transistors outputs (terminals 6, 7 and 8 on Figure 1), fully programmable,
see “6.27.- PROGRAMMING ALARM 3 (DIGITAL OUTPUT T1)” and “6.28.- PROGRAMMING ALARM 4 DIGITAL
OUTPUT T2)”.
47
Instruction Manual
CVM-C11