6.1.- PRIMARY VOLTAGE
On this screen the voltage transformer primary is programmed.
Press the key for 3 seconds to enter the edit mode. The prog icon will flash on the left of the
screen.
Press the key to modify the value of the flashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop flashing.
If the value entered by the user is out of the range of programming values, the programmed value will
be deleted and the system will restore it to the last saved value.
Configuration values
Table 21: Configuration values: Primary voltage.
Primary voltage
Minimum value 1 V
Maximum value
99999 V
Voltage ratio ≤ 1000.
Voltage ratio x Current ratio ≤ 300000.
Note: The ratio is the relation between the primary and the secondary.
Press key to access the next programming step.