Configuration values
Table 23: Configuration values: Primary current.
Primary current
Minimum value 1 A
Maximum value
10000 A
Voltage ratio x Current ratio ≤ 300000.
Note: The ratio is the relation between the primary and the secondary.
Press key   to access the next programming step.
 
 6.4.- SECONDARY CURRENT (MODEL CVM-E3-MINI-ITF)
Note: Display visible on models: CVM-E3-MINI-ITF and CVM-E3-MINI-ITF-WiEth.
On this screen the current transformer secondary is selected.
Press the   key for 3 seconds to enter the edit mode. The prog icon will flash on the left of the 
screen.
Use the   key to browse the available options.
 
 Configuration values
Table 24: Configuration values: Secondary current.
Secondary current
Possible values 1 A 5 A
Voltage ratio x Current ratio ≤ 300000. 
To validate the value, press the   key for 3 seconds; the prog icon will stop flashing.
Press key   to access the next programming step.
58
CVM-E3-MINI
Instruction Manual