6.18.6. LATCH TIME
Note: Screen visible if the latch has been enabled, see “6.18.5. LATCH”.
This screen is used to program the latch time, meaning the time in seconds when the alarm will be 
latched. After this time, if the alarm condition has cleared, the disconnection delay is activated
Press the   key for 3 seconds to enter the edit mode. The prog icon will flash on the left of the 
screen.
Use the   key to browse the available options.
 Configuration values
Table 44: Configuration values: Latch time.
Latch time
Minimum value 0 s.
Maximum value 600 s.
Note: If a 0 is programmed, the alarm remains latched and can only be unlatched manually.
To validate the value, press the   key for 3 seconds; the prog icon will stop flashing.
Press key   to access the next programming step.
6.18.7.  DISCONNECTION TIME DELAY
The alarm disconnection delay is programmed on this screen in seconds.
Press the   key for 3 seconds to enter the edit mode. The prog icon will flash on the left of the 
screen.
Press the   key to modify the value of the flashing digit.
When the desired value is shown on the screen, use the   and   keys to move the edit cursor.
73
Instruction Manual
CVM-E3-MINI