7.3.8. DIGITAL INPUT: PULSE COUNTER
The functions 0x04 and 0x10 are implemented for this variable.
If the Digital Input has been configured as Pulse Counter, the value of the counter is displayed in this 
variable.
Table 77:Modbus memory map: Pulse counter.
Pulse counter
Variable Format Address
Digital input pulse counter Uint [64] 4E23 -  4E24 - 4E25 -  4E26 
7.3.9. DEVICE CONFIGURATION VARIABLES.
The functions 0x04 and 0x10 are implemented for this variable.
The device’s Modbus function does not check whether the variables recorded are within the correct 
margins, they are only checked when they are read from the EEPROM. So if any parameter is recorded 
with an incorrect value the device will be configured with its default value.
The Modbus configuration will not take effect until the device is reset.
7.3.9.1. Transformation ratios.
Table 78: Modbus memory map: Transformation ratios.
Transformation ratios
Configuration variable 
(7)
Address  Valid data margin Default value
Voltage primary  2710 - 2711 1 - 599999 1
Voltage secondary 2712 1 - 999 1
Current primary 
(8)
2713 1 - 10000 5
Current secondary 
(9)
2714
0: .../1A
1: ../5 A
1
(7) 
 Voltage ratio x Current ratio ≤ 300000. 
    Voltage ratio ≤ 1000.
(8)
 Configurable parameter in the models: CVM-E3-MINI-ITF, CVM-E3-MINI-ITF-WiEth, CVM-E3-MINI-MC and CVM-E3-
MINI-MC-WiEth.
(9) 
Configurable parameter in the models: CVM-E3-MINI-ITF and CVM-E3-MINI-ITF-WiEth.
Note: The ratio is between the primary and the secondary.
Note: The 5 registers must be written or read at once (as a group); otherwise. the system will respond 
with an error.
7.3.9.2. Flex sensor type (Models CVM-E3-MINI-FLEX  and CVM-E3-MINI-FLEX-WiEth)
Table 79: Modbus memory map: Flex sensor type.
Tipo de sensor Flex
Configuration variable Address Valid data margin Default value
Flex sensor  2756
0: 100 uV/A
1: 76 uV/A
0
98
CVM-E3-MINI
Instruction Manual