7.3.9.3. Number of quadrants
Table 80: Modbus memory map: Number of quadrants
Numberof quadrants
Configuration variable Address Valid data margin Default value
Number of quadrants 2B64
0: 4 quadrants
1: 2 quadrants
0
7.3.9.4. Measurement convention
Table 81: Modbus memory map: Measurement convention.
Measurement convention
Configuration variable Address Valid data margin Default value
Measurement convention 2B86
0: Circutor
1: IEC
2: IEEE
0
7.3.9.5. Measurement system
Table 82: Modbus memory map: Measurement system
Measurement system
Configuration
variable
Address Valid data margin
Default
value
Measurement system 2B5C
0: 4-3Ph Three-phase network with 4 wires.
1: 3-3Ph Three-phase network with 3 wires.
2: 3-ArOM Three-phase network with 3 wires, Aron.
(10)
3: 3-2Ph Two-phase network with 3 wires.
4: 2-2Ph Single-phase network with 2 wires, phase-to-phase.
5: 2-1Ph Single-phase network with 2 wires, phase-to-neutral.
0
(10)
Option not available for the CVM-E3-MINI-FLEX and CVM-E3-MINI-FLEX-WiEth models.
7.3.9.6. Maximum demand
Table 83: Modbus memory map: Maximum demand
Maximum demand
Configuration variable Address Valid data margin
Default
value
Integration period 274C
0: The maximum demand will not be calculated
1 - 60 minutes
0
7.3.9.7. Display backlight
Table 84: Modbus memory map: Backlight
Backlight
Configuration variable Address Valid data margin Default value
Backlight 2B5E 1 - 999 seconds 300 s
7.3.9.8. Activating the harmonics display screen
Table 85: Modbus memory map: Display of harmonics
Display of harmonics
Configuration variable Address Valid data margin Default value
Display of harmonics 2B62
0: No
1: Yes
0
99