Press the key for 3 seconds to enter the edit mode. The prog icon will flash on the left of the
screen.
Press the key to modify the value of the flashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
Configuration values
Table 47: Configuration values: Kilowatts per pulse.
Kilowatts per pulse
Minimum value 000.01 kWh.
Maximum value 999.99 kWh
To validate the value, press the key for 3 seconds; the prog icon will stop flashing.
If the value entered by the user is out of the range of programming values, the programmed value will
be deleted and the system will restore it to the last saved value.
Press key to access the next programming step.
6.18.10. PULSE WIDTH
Note: This screen is displayed if the alarm parameter has been selected from an energy value, see
Table 40.
The width of the pulse is selected on this screen in ms.
Press the key for 3 seconds to enter the edit mode. The prog icon will flash on the left of the
screen.
Press the key to modify the value of the flashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
75
Instruction Manual
CVM-E3-MINI