Press the   key for 3 seconds to enter the edit mode. The prog icon will flash on the left of the 
screen.
Press the   key to modify the value of the flashing digit.
When the desired value is shown on the screen, use the   and   keys to move the edit cursor.
To validate the value, press the   key for 3 seconds; the prog icon will stop flashing.
 Configuration values
Table 42: Configuration values: Hysteresis.
Hysteresis
Minimum value 0 %
Maximum value
99 %
Press key   to access the next programming step.
6.18.5. LATCH
The interlocking is selected on this screen, i.e., if the alarm is interlocked after it has been tripped, 
even when the condition that triggered it has disappeared.
Press the   key for 3 seconds to enter the edit mode. The prog icon will flash on the left of the 
screen.
Use the   key to browse the available options.
 Configuration values
Table 43: Configuration values: Latch.
Latch
Possible values Yes No
To validate the value, press the   key for 3 seconds; the prog icon will stop flashing.
Press key   to access the next programming step.
Note: If the device is reset, the status of alarms is deleted and all alarms will return to the programmed 
standby status, provided that the condition that triggered them has been resolved.
72
CVM-E3-MINI
Instruction Manual